Welcome to our websites!

WP8300 Series Isolated Safety Barrier

Short Description:

The WP8300 series of safety barrier is designed to transmit analog signal generated by a transmitter or temperature sensor between the hazardous area and safe area. The product can be mounted by 35mm DIN railway, requiring separate power supply and Insulated among input, output and supply.


Product Detail

Product Tags

Description

The series has four major models:

 
WP8310 and WP8320 correspond to measuring side and operating side safety barrier. WP 8310 processes and transmits signal from the transmitter located in hazardous zone to systems or other instruments in security zone, while WP8320 conversely receives signal from security zone and outputs to hazardous zone. Both Models only receive DC signal.

 
WP8360 and WP8370 receive thermocouple and RTD signals from hazardous zone respectively, perform isolated amplification and output the converted current or voltage signal to security zone.

 
All of the WP8300 series safety barriers can have single or dual output and uniform dimension of 22.5*100*115mm. However WP8360 & WP8370 only accept single input signal while WP8310 & WP8320 can also receive dual input.

Specification

Item name Isolated Safety Barrier
Model WP8300 Series
Input impedance Measuring side safety barrier ≤ 200Ω

Operating side safety barrier ≤ 50Ω

Input signal 4~20mA, 0~10mA, 0~20mA (WP8310, WP8320);

Thermocouple Grade K, E, S, B, J, T, R, N (WP8260);

RTD Pt100, Cu100, Cu50, BA1, BA2 (WP8270);

Input power 1.2~1.8W
Power supply 24VDC
Output signal 4~20mA, 0~10mA, 0~20mA, 1~5V, 0~5V, 0~10V, customized
Output load Current type RL≤ 500Ω, Voltage type RL≥ 250kΩ
Dimension 22.5*100*115mm
Ambient temperature 0~50℃
Installation DIN 35mm rail
Accuracy 0.2%FS

  • Previous:
  • Next:

  • Write your message here and send it to us