WP-L Flow indicator/ Flow totalizer
Shanghai Wangyuan WP-L Flow totalizer is suitable for measuring all kinds of liquids, steam, general gas and etc. This instrument has been widely used for flow totalizing, measurement and control in biology, petroleum, chemical, metallurgy, electric power, medicine, food, energy management, aerospace, machinery manufacture and other industries.
1.System stability, reliability and safety of the instrument are greatly improved by using single-chip microprocessor control.
2.Various input signal, matching with differential pressure transmitters, pressure transmitters, frequency flow sensors and etc. (such as vortex flowmeter, turbine flowmeter…)
3.Using advanced microprocessor technology, our flow totalizer can cater to various compensation of different primary instruments
4.Simple programming, easy operation, multiple functions, good general performance, automatic compensation of pressure and temperature
5.The type of channel input signals can be set and changed freely via inner parameters
6.Multiprocessor communication is available, with variety of standard serial output, communication baud rate 300~9600bps inner parameters of totalizer can be set freely, communicate with various serial input/output devices (like computer, programmable controller, PLC and etc.), informing energy measurement and management system. Equipped with third party industrial control configuration software, conveniently connect with host computer do network monitoring management.
7.Can be connected directly with serial micro printer, to realize instant print and timed print of instant flow measurement value, time, the cumulative value, whole 9 bits flow total cumulative value, flow (differential pressure, frequency) input value, pressure compensation input values, temperature compensation input value.
WP-L C80 size 160*80mm
WP-L S80 size 80*160mm
WP-L 90 size 96*96mm
Table1 - Communication |
||||||
Code |
0 |
2 |
3 |
4 |
8 |
9 |
Communication |
No |
RS-232 |
Print port |
RS-422 |
RS-485 |
Customize |
Table2 -Output |
|||||
Code |
0 |
2 |
3 |
4 |
5 |
Output |
No |
4-20mA |
0-10mA |
1-5V |
0-5V |
Table3 -Input |
||||||
Code |
Input |
Measure range |
Code |
Input |
Measure range |
Note |
A |
4-20mA |
-19999~99999d |
O |
Impulse-collector open circuit |
0-10kHz |
Value in this table is max range, user can revise secondary parameters to confirm range. |
B |
0-10mA |
-19999~99999d |
G |
Pt100 |
-200~650℃ |
|
C |
1-5V |
-19999~99999d |
E |
Thermocouple E |
0-1000℃ |
|
D |
0-5V |
-19999~99999d |
K |
Thermocouple K |
0-1300℃ |
|
M |
0-20mA |
-19999~99999d |
R |
Customize |
-19999~99999d |
|
F |
Impulse |
0-10kHz |
N |
No Compensation input |